Volume 29, 2019 Volume 28, 2018 Volume 27, 2017 Volume 26, 2016 Volume 25, 2015 Volume 24, 2014 Volume 23, 2013 Volume 22, 2012 Volume 21, 2011 Volume 20, 2010 Volume 19, 2009 Volume 18, 2008 Volume 17, 2007 Volume 16, 2006 Volume 15, 2005 Volume 14, 2004 Volume 13, 2003 Volume 12, 2002 Volume 11, 2001 Volume 10, 2000 Volume 9, 1999 Volume 8, 1998 Volume 7, 1997 Volume 6, 1996 Volume 5, 1995 Volume 4, 1994 Volume 3, 1993 Volume 2, 1992 Volume 1, 1991

Atomization and Sprays

DOI: 10.1615/AtomizSpr.2017019352
pages 665-690

EXPERIMENTAL INVESTIGATION OF THE 700 MWe CONTAINMENT SPRAY SYSTEM SPRAY NOZZLES/SYSTEM

Manish Jain
Department of Mechanical Engineering, I.I.T., Bombay, Powai, Mumbai, India
T. K. Kandar
Directorate of Technology Development, Nuclear Power Corporation of India Limited, Mumbai, India
S. F. Vhora
Directorate of Technology Development, Nuclear Power Corporation of India Limited, Mumbai, India
Kannan Iyer
Indian Institute of Technology Bombay, Main Gate Rd, IIT Area, Powai, Mumbai, Maharashtra 400076
S. V. Prabhu
Department of Mechanical Engineering, I.I.T., Bombay, Powai, Mumbai, India

RÉSUMÉ

The aim of the present work is to study a full cone pressure swirl nozzle (pressure swirl nozzles) and its configuration on a spray header for the 700MWe Indian Pressurized HeavyWater Reactor (IPHWR) Containment Spray System (CSS) (a FOAK system). The Reynolds number (Re) effect on coefficient of discharge (Cd), spray cone angle, SMD (D32), droplet size distribution, and droplet velocity is investigated for full cone pressure swirl nozzles. Studies are performed to optimize the nozzle configuration on the spray header and the distribution of mass flux. The mass flux density studies are carried out in patternater facilities at IIT Bombay and the Kakrapar Atomic Power Project (KAPP). Water at room temperature is used for the spray in experimental investigation. The nozzle characterization experimental studies are carried out for Re ranging from 1.43 × 105 to 2.49 × 105. A particle droplet image analyzer (PDIA) is used for the measurement of droplet velocity, SMD (D32), and drop size distributions. A simple CCD camera along with a diode laser and patternater software is used for the measurement of the spray cone angle. The catch and time technique is used to measure coefficient of discharge. The droplet flux distribution at different Z/D0 and R/D0 is also performed. Nukiyama-Tanasawa distribution and log-normal peak shifted distribution show a reasonably good confirmation with the present experimental studies.