International Symposium on Multiphase Flow and Transport Phenomena
DOI: 10.1615/ICHMT.1997.IntSymLiqTwoPhaseFlowTranspPhen
ISBN Print: 1-56700-162-9
DEVELOPMENT AND EVALUATION OF A TWO-PHASE LOOP-TYPE THERMOSYPHON FOR COOLING TELECOMMUNICATIONS SYSTEM
page 9
DOI: 10.1615/ICHMT.1997.IntSymLiqTwoPhaseFlowTranspPhen.230
SINOPSIS
In the present study, a two-phase loop thermosyphon, which the evaporator and condenser sections of the system connected by means of two separate flow tubes for concurrent natural circulation of the working fluid, was designated. The thermal performance was obtained in a heat flux of up to 8 W/cm2 with an overall temperature difference of 50 °C under the condition of forced convection mode of the condenser section.