ADVANCED INDOOR HUMIDITY CONTROL: NEW IMPACTS ON CONJUGATED HEAT AND MASS TRANSFER
SINOPSIS
Fluid flow and conjugate heat and mass transfer in a hollow fiber membrane contactor used for air humidification are investigated. The contactor is like a shell-and-tube heat exchanger where the water stream flows in the tube side while the air stream flows in the shell side in a counter flow arrangement. To overcome the difficulties in direct modeling of the whole contactor a representative cell comprised of a single fiber, with the water flowing inside the fiber and the air stream flowing outside the fiber, is considered. The air stream outside the fiber has an outer free surface. Furthermore, the equations governing the fluid flow and heat and mass transfer in the two streams are combined together with the heat and mass diffusion equations in membranes. The conjugate problem is then solved to obtain the velocity, temperature, and concentration distributions in the two fluids and in the membrane. The local and mean Nusselt and Sherwood numbers in the cell are then obtained and experimentally validated.
-
Zhang Li-Zhi, Yuan Wu-Zhi, Three-dimensional pore-scale flow and mass transport through composite asymmetric membranes, Science and Technology for the Built Environment, 23, 1, 2017. Crossref